- Description
- Specifications
FLT-CP-3S-350 Compact Set Phoenix Surge protection 100 kA (All) ใช้กับตู้ MDB แบบสายนิวตรอนแยกกับสายกราวด์
ระบบไฟฟ้าแบบ TN-S or 3 PHASE 5 WIRE 5-conductor system; L1, L2, L3, N, PE
Surge protection and interference filters Surge protection for the power supply unit
Type 1 lightning arresters FLASHTRAB compact PLUS
– Seamless pluggability (even for N/PE spark gap)
– Thermal disconnect device for each individual connector
– Optical, mechanical status indication for the individual arresters
– With floating remote indication contact
– Connectors can be checked with CHECKMASTER
– High continuous voltage of 350 V AC for 230/400 V AC networks with high voltage fluctuations
Electrical data
IEC category / EN type | I + II / T1 + T2 |
Nominal voltage UN | 240 V AC (230/400 V AC ... 240/415 V AC) |
Maximum continuous operating voltage UC L-N / N-PE / L-PEN |
350 V AC / 350 V AC / - |
Lightning test curr. Iimp (10/350) μs | |
Peak value | 100 kA |
Charge | 50 As |
Specific energy | 2.50 MJ/Ω |
Nominal discharge surge current In (8/20) μs L-N / N-PE / L-PEN |
25 kA / 100 kA / - |
Follow current quenching capacity Ifi L-N / N-PE / L-PEN |
25 kA (264 V AC) / 100 A / - |
Protection level UP L-N / N-PE / L-PEN |
≤ 1.5 kV / ≤ 1.5 kV / - |
Response time tA L-N / N-PE / L-PEN | ≤ 25 ns / ≤ 100 ns / - |
Backup fuse max. in acc. with IEC | 315 A (gL/gG) |
Immunity to short-circuiting (with max. backup fuse) IP |
25 kA |
General data | |
Dimensions W / H / D | 142.8 mm / 95.8 mm / 70 mm |
Connection data solid / stranded / AWG | 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 |
Temperature range | -40 °C ... 80 °C |
Inflammability class in acc. with UL 94 | V0 |
Test standards | IEC 61643-1 / EN 61643-11 / UL 1449 |