FLT-CP-PLUS-3S-350 Compact Set Phoenix Surge protection 100 kA (All) ใช้กับตู้ MDB แบบสายนิวตรอนแยกกับสายกราวด์
ระบบไฟฟ้าแบบ TN-S or 3 PHASE 5 WIRE 5-conductor system; L1, L2, L3, N, PE
Surge protection and interference filters Surge protection for the power supply unit
Type 1 lightning arresters FLASHTRAB compact PLUS
– Seamless pluggability (even for N/PE spark gap)
– Thermal disconnect device for each individual connector
– Optical, mechanical status indication for the individual arresters
– With floating remote indication contact
– Connectors can be checked with CHECKMASTER
– High continuous voltage of 350 V AC for 230/400 V AC networks with high voltage fluctuations
Electrical data
| IEC category / EN type |
I / T1 |
| Nominal voltage UN |
240 V AC (230/400 V AC ... 240/415 V AC) |
|
Maximum continuous operating voltage UC
L-N / N-PE / L-PEN
|
350 V AC / 350 V AC / - |
| Lightning test curr. Iimp (10/350) μs |
|
| Peak value |
100 kA |
| Charge |
50 As |
| Specific energy |
2.50 MJ/Ω |
|
Nominal discharge surge current In (8/20) μs
L-N / N-PE / L-PEN
|
25 kA / 100 kA / - |
|
Follow current quenching capacity Ifi
L-N / N-PE / L-PEN
|
50 kA (264 V AC) / 100 A / - |
|
Protection level UP L-N / N-PE / L-PEN
|
≤ 1.5 kV / ≤ 1.5 kV / - |
| Response time tA L-N / N-PE / L-PEN |
≤ 100 ns / ≤ 100 ns / - |
| Backup fuse max. in acc. with IEC |
315 A (gL/gG) |
|
Immunity to short-circuiting
(with max. backup fuse) IP
|
50 kA |
| General data |
|
| Dimensions W / H / D |
142.8 mm / 97 mm / 71.5 mm |
| Connection data solid / stranded / AWG |
2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 |
| Temperature range |
-40 °C ... 80 °C |
| Inflammability class in acc. with UL 94 |
V0 |
| Test standards |
IEC 61643-1 / EN 61643-11 / EN 61643-11/A11 /UL 1449 |